ADE7751
V1A
V1A
FILTER
AND
FAULT
Ib
CT
Rf
V1A
V1B
V1A
A
COMPARE
PHASE
Rb
V1A
Cf
AGND
V1N
0V
V1B
V1B
B
TO
MULTIPLIER
TEST
CURRENT
Ib
AGND
Rb
0V
V1N
Cf
NEUTRAL
V1B < 87.5% OF V1A
Figure 13. Fault Conditions for Inactive Input
Less than Active Input
Ra
CT
Rb
Cf
Rf
V1B
Rf;
Fault with V1B Greater than V1A
Figure 14 illustrates another fault condition. If V1A is the active
input (i.e., is being used for billing) and the voltage signal on
V1B (inactive input) becomes greater than 114% of V1A, the
FAULT indicator goes active, and there is also a swap over to
V
240Vrms
NOTE
Ra
Rb + VR = R f
VR
Rf
V2P
V2N
Cf
the V1B input. The analog input V1B has now become the
active input. Again there is a time delay of about 1.2 seconds
associated with this swap. V1A will not swap back to being the
active channel until V1A becomes greater than 114% of V1B.
However, the FAULT indicator will become inactive as soon as
V1A is within 12.5% of V1B. This threshold eliminates poten-
tial chatter between V1A and V1B.
Figure 15. Fault Conditions for Inactive
Input Greater than Active Input
TRANSFER FUNCTION
Frequency Outputs F1 and F2
The ADE7751 calculates the product of two voltage signals (on
Channel 1 and Channel 2) and then low-pass filters this product
to extract real power information. This real power information
is then converted to a frequency. The frequency information is
V1B
V1A
FILTER
AND
FAULT
output on F1 and F2 in the form of active low pulses. The pulse
0V
V1A
AGND
V1A
V1N
V1B
A
B
COMPARE
TO
MULTIPLIER
rate at these outputs is relatively low, e.g., 0.34 Hz maximum for
ac signals with S0 = S1 = 0 (see Table III). This means that the
frequency at these outputs is generated from real power informa-
tion accumulated over a relatively long period of time. The result is
an output frequency that is proportional to the average real
V1A < 87.5% OF V1B
OR
V1B > 114% OF V1A
V1B
power. The averaging of the real power signal is implicit to the
digital-to-frequency conversion. The output frequency or pulse
rate is related to the input voltage signals by the following equation.
Freq =
V REF
Figure 14. Fault Conditions for Inactive Input
Greater than Active Input
Calibration Concerns
Typically, when a meter is being calibrated, the voltage and current
where,
Freq = Output frequency on F1 and F2 (Hz)
5 . 74 × V 1 × V 2 × Gain × F 1 – 4
2
(7)
circuits are separated as shown in Figure 15. This means that
current will only pass through the phase or neutral circuit. Figure 15
shows current being passed through the phase circuit. This is the
V 1
V 2
= Differential rms voltage signal on Channel 1 (Volts)
= Differential rms voltage signal on Channel 2 (Volts)
preferred option since the ADE7751 starts billing on the input
V1A on power-up. The phase circuit CT is connected to V1A in
Gain = 1, 2, 8, or 16, depending on the PGA gain selection
made using logic inputs G0 and G1
the diagram. Since there is no current in the neutral circuit, the
FAULT indicator will come on under these conditions. However,
this does not affect the accuracy of the calibration and can be
used as a means to test the functionality of the fault detection.
If the neutral circuit is chosen for the current circuit in the
arrangement shown in Figure 15, it may have implications for
V REF
F 1–4
= The reference voltage (2.5 V ± 8%) (Volts)
= One of four possible frequencies selected by using the
logic inputs S0 and S1 (see Table II)
Table II.
the calibration accuracy. The ADE7751 will power up with the
V1A input active as normal. However, since there is no current
in the phase circuit, the signal on V1A is zero. This will cause a
FAULT to be flagged and the active input to be swapped to V1B
(Neutral). The meter may be calibrated in this mode, but the
phase and neutral CTs may differ slightly. Since under no-fault
conditions all billing is carried out using the phase CT, the meter
S1
0
0
1
1
S0
0
1
0
1
F 1–4 (Hz)
1.7
3.4
6.8
13.6
XTAL/CLKIN *
3.579 MHz/2 21
3.579 MHz/2 20
3.579 MHz/2 19
3.579 MHz/2 18
should be calibrated using the phase circuit. Of course, both
phase and neutral circuits may be calibrated.
* F 1–4 are a binary fraction of the master clock and will thus vary if the specified
CLKIN frequency is altered.
–14 –
REV. 0
相关PDF资料
EVAL-ADE7752AEBZ BOARD EVALUATION FOR ADE7752A
EVAL-ADE7753ZEB BOARD EVALUATION AD7753
EVAL-ADE7754EBZ BOARD EVALAUTION FOR ADE7754
EVAL-ADE7755ZEB BOARD EVALUATION FOR AD7755
EVAL-ADE7758ZEB BOARD EVAL FOR AD7758
EVAL-ADE7759EBZ BOARD EVALUATION FOR ADE7759
EVAL-ADE7762EBZ BOARD EVALUATION FOR ADE7762
EVAL-ADE7763ZEB BOARD EVALUATION FOR ADE7763
相关代理商/技术参数
EVAL-ADE7752AEB 制造商:Analog Devices 功能描述:EVAL BD THREE PHASE ACTIVE ENERGY MET IC - Bulk
EVAL-ADE7752AEBZ 功能描述:BOARD EVALUATION FOR ADE7752A RoHS:是 类别:编程器,开发系统 >> 评估演示板和套件 系列:- 标准包装:1 系列:- 主要目的:电信,线路接口单元(LIU) 嵌入式:- 已用 IC / 零件:IDT82V2081 主要属性:T1/J1/E1 LIU 次要属性:- 已供物品:板,电源,线缆,CD 其它名称:82EBV2081
EVAL-ADE7752EB 制造商:AD 制造商全称:Analog Devices 功能描述:Three Phase Energy Metering IC with Pulse Output
EVAL-ADE7753ZEB 功能描述:BOARD EVALUATION AD7753 RoHS:是 类别:编程器,开发系统 >> 评估演示板和套件 系列:- 标准包装:1 系列:- 主要目的:电信,线路接口单元(LIU) 嵌入式:- 已用 IC / 零件:IDT82V2081 主要属性:T1/J1/E1 LIU 次要属性:- 已供物品:板,电源,线缆,CD 其它名称:82EBV2081
EVAL-ADE7754EB 制造商:Analog Devices 功能描述:EVALUATION BOARD FOR POWER METERING, POLYPHASE MULTIFUNCTION ENERGY METERING IC WITH SERIAL PORT 制造商:Analog Devices 功能描述:PWR METERING, POLYPHASE MULTIFUNCTION ENERGY METERING IC W/ - Bulk
EVAL-ADE7754EBZ 功能描述:BOARD EVALAUTION FOR ADE7754 RoHS:是 类别:编程器,开发系统 >> 评估演示板和套件 系列:- 标准包装:1 系列:- 主要目的:电信,线路接口单元(LIU) 嵌入式:- 已用 IC / 零件:IDT82V2081 主要属性:T1/J1/E1 LIU 次要属性:- 已供物品:板,电源,线缆,CD 其它名称:82EBV2081
EVAL-ADE7755EB 制造商:Analog Devices 功能描述:EVAL BOARD ENERGY METERINGW/PULSE OUTPUT - Bulk
EVAL-ADE7755EBZ 制造商:AD 制造商全称:Analog Devices 功能描述:Energy Metering IC with Pulse Output